Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2019, 06:16 PM
  • D 0074_D 0073_9182019_122802.mp4

Date
09/18/2019
W/O
0792816
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00154
PipeID
P09974
Time
11:16 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8084
Sewer Name
D JOINT OUTFALL D - UNIT 4
City
LAWNDALE
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20190918DF_JOINT_OUTFALL_D_UNIT_4
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
D 0074
Downstream MH
D 0073
Dir. of Survey
Downstream
Length Surveyed
326.6 ft.
Total Length
326.6 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole D 0074 to D 0073
MH: D 0074MH: D 0073downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:00 PM0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 45% MAG2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.6 ft. MGP - General Photograph129.8 ft. MGP - General Photograph172 ft. MGP - General Photograph228.9 ft. MGP - General Photograph310.5 ft. MGP - General Photograph322.9 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 55% MAG322.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.6 ft. MGO - General Observation - Grease Throughout The Reach (5%)326.6 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach326.6 ft. AMH - Downstream Manhole, Survey Ends - 12:50 PM

Observation photos (8)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 45% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 45% MAG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    40.6 ft. - General Photograph

  • General Photograph

    129.8 ft. - General Photograph

  • General Photograph

    172 ft. - General Photograph

  • General Photograph

    228.9 ft. - General Photograph

  • General Photograph

    310.5 ft. - General Photograph

Observations (20)

DistanceCodeObservation
2SAP
326.6MGOGrease Throughout The Reach (5%)
322.9SZ55% MAG
0MWL
0AMH12:00 PM
322.9SAP
0MWM
2SZ45% MAG
2MGOConn. @ Mh, 3 O' Clock. Active
326.6MGOPeeling & Flaking Throughout The Reach
322.9SRV
2SRV
322.9SSS
40.6MGP
228.9MGP
326.6AMH12:50 PM
172MGP
310.5MGP
2SSS
129.8MGP

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-09-18T11:16:40-07:00
documentation
FRANKLIN, BRAR, IGNACIO, RUVALCABA
is_lateral_inspection
false