Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2019, 03:59 PM
  • D 0077_D 0076_9182019_100701.mp4

Date
09/18/2019
W/O
0792816
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00154
PipeID
P09977
Time
8:59 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8084
Sewer Name
D JOINT OUTFALL D - UNIT 4
City
LAWNDALE
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20190918DF_JOINT_OUTFALL_D_UNIT_4
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
D 0077
Downstream MH
D 0076
Dir. of Survey
Downstream
Length Surveyed
220.2 ft.
Total Length
220.2 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole D 0077 to D 0076
MH: D 0077MH: D 0076downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:03 AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0.1 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start45.5 ft. MGP - General Photograph103.1 ft. MGO - General Observation - ABANDONED MH148.7 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"204.8 ft. MGP - General Photograph218.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish218.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish218.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish218.6 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 75% MAG220.2 ft. MWL - Water Level, 20 %of cross sectional area220.2 ft. MGO - General Observation - Grease Throughout The Reach (5%)220.2 ft. AMH - Downstream Manhole, Survey Ends - 10:33 AM220.2 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach

Observation photos (12)

  • Upstream Manhole, Survey Begins - 9:03 AM

    0 ft. - Upstream Manhole, Survey Begins - 9:03 AM

  • General Observation - Conn. @ Mh, 3 O' Clock. Active

    0 ft. - General Observation - Conn. @ Mh, 3 O' Clock. Active

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    45.5 ft. - General Photograph

  • General Observation - ABANDONED MH

    103.1 ft. - General Observation - ABANDONED MH

  • Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"

    148.7 ft. - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"

  • General Photograph

    204.8 ft. - General Photograph

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    218.6 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    218.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (19)

DistanceCodeObservation
0.1MWM
218.6SRV
220.2MWL
220.2MGOGrease Throughout The Reach (5%)
2SSS
218.6SSS
0AMH9:03 AM
0MGOConn. @ Mh, 3 O' Clock. Active
103.1MGOABANDONED MH
218.6SAV
2SRV
2SZ75% MAG
220.2AMH10:33 AM
204.8MGP
148.7TFA
2SAV
220.2MGOPeeling & Flaking Throughout The Reach
218.6SZ75% MAG
45.5MGP

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-09-18T08:59:54-07:00
documentation
FRANKLIN, BRAR, IGNACIO, RUVALCABA
is_lateral_inspection
false