Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2019, 04:41 AM
  • 18 0503_18 0502 _18072019_215759.mp4

Date
07/18/2019
W/O
776971
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00705
PipeID
P14357
Time
9:41 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6639
Sewer Name
18 SOUTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_776971_TV18180_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0503
Downstream MH
18 0502
Dir. of Survey
Downstream
Length Surveyed
501.4 ft.
Total Length
501.4 ft.
Structural Index
3
Structural Quick
413Q
Structural Rating
281
O&M Index
2
O&M Quick
2S00
O&M Rating
200
Overall Index
2
Overall Quick
Overall Rating
481
Pipe schematic from manhole 18 0503 to 18 0502
MH: 18 0503MH: 18 0502downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 05030 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start35.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES39.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES43.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start52.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"90.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"375.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"386.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES387.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"499.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish499.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish501.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0502501.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    35.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    39.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    43.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    386.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    501.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
90.5TBA
43.5CM
0AMH18 0503
501.4AMH18 0502
499.7CM
0MWL
0MGOCOCKROACHES IN MANHOLE
501.4MGOCOCKROACHES IN MANHOLE
140.2TBA
386.3FM
375.5TBA
0MWM
2DAGS
39.5CL
387.3TBA
499.7DAGS
35.1CL
52.9TBA

Properties (6)

additional_info
SC378306
custom_field_two
3
customer
LACSD
datetime
2019-07-18T21:41:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false