Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 25, 2019, 05:29 PM
  • H 0646_H 0645_9252019_105938.mp4

Date
09/25/2019
W/O
0792939
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00192
PipeID
P11052
Time
10:29 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8092
Sewer Name
H JOINT OUTFALL H - UNIT 8J
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20190925SHO_JOINT_OUTFALL_H_UNIT_8J
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
H 0646
Downstream MH
H 0645
Dir. of Survey
Downstream
Length Surveyed
119.9 ft.
Total Length
119.9 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole H 0646 to H 0645
MH: H 0646MH: H 0645downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 06462.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start60.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"119.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish119.9 ft. AMH - Downstream Manhole, Survey Ends - MH 0645119.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (9)

DistanceCodeObservation
119.9SSS
119.9AMHMH 0645
2.6SAV
0MWM
119.9SAV
60.9TF
0MWL
2.6SSS
0AMHMH 0646

Properties (5)

additional_info
RFIR
customer
LACSD
datetime
2019-09-25T10:29:41-07:00
documentation
OBREGON, BRAR, RUVALCABA
is_lateral_inspection
false