Wastewater/Activity/PacpInspection/1.0Sep 17, 2019, 07:25 AM
  • Section#1_02 0927_02 0926__9172019__I0238.mp4

Date
09/17/2019
W/O
0790965
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00252
PipeID
P03495
Time
12:25 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0238
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20190917MDM_DOWNEY_BELLFLOWER_DIVERSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0927
Downstream MH
02 0926
Dir. of Survey
Downstream
Length Surveyed
348.5 ft.
Total Length
348.5 ft.
Structural Index
3
Structural Quick
3C29
Structural Rating
78
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
78
Pipe schematic from manhole 02 0927 to 02 0926
MH: 02 0927MH: 02 0926downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM0 ft. MWM - Water Mark, 40 %of cross sectional area12.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - SLIGHT17.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish - SLIGHT23 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE28 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H32.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H37.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL43.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL53 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H58.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H59.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - H63.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL68.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL83.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H109 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL116.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL127 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL131.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL152.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H157.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H204.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H218.9 ft. RPP - Repair Patch, from 01 to 02 o'clock, within 8 inches of joint: YES - BRICK & CONCRETE PLUG POSSIBLE266.2 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - H275 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL284 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H285.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL287.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H325.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL336.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL341.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H341.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL348.5 ft. AMH - Downstream Manhole, Survey Ends - 1:35AM

Observation photos (9)

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    12.2 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    37.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H

    53 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL

    63.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    109 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    127 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H

    152.2 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H

  • Repair Patch, from 01 to 02 o'clock, within 8 inches of joint: YES - BRICK & CONCRETE PLUG POSSIBLE

    218.9 ft. - Repair Patch, from 01 to 02 o'clock, within 8 inches of joint: YES - BRICK & CONCRETE PLUG POSSIBLE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    336.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

Observations (34)

DistanceCodeObservation
59.8FLH
58.1FLH
37.8FLSL
325.7FCSL
285.2FCSL
17.2FLSLIGHT
127FLSL
152.2FCH
32.7FLH
53FLH
284FCH
109FLSL
204.7FCH
131.6FLSL
63.4FLSL
116.7FLSL
0MWL
83.1FCH
23FCHAIRLINE
28FLH
157.4FLH
341.3FLH
275FCSL
12.2FLSLIGHT
266.2FLH
43.7FLSL
68.4FCSL
287.5FLH
348.5AMH1:35AM
218.9RPPBRICK & CONCRETE PLUG POSSIBLE
0AMH12:55AM
341.3FLSL
0MWM
336.1FLSL

Properties (5)

custom_field_three
SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2019-09-17T00:25:23-07:00
is_lateral_inspection
false