Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2019, 06:58 AM
  • 02 1146_02 1145 _01082019_002458.mp4

Date
07/31/2019
W/O
777518
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00351
PipeID
P02930
Time
11:58 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5945
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_777518_TV02244_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1146
Downstream MH
02 1145
Dir. of Survey
Downstream
Length Surveyed
321.4 ft.
Total Length
321.4 ft.
Structural Index
3
Structural Quick
4233
Structural Rating
19
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 02 1146 to 02 1145
MH: 02 1146MH: 02 1145downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 11468.5 ft. CM - Crack Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES10.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES11.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES23.6 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES33 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start239.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start239.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED321.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED321.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1145

Observation photos (9)

  • General Observation - CONNECTION AT MH 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH 3 O'CLOCK

  • Crack Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

    8.5 ft. - Crack Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    10.8 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    11.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

    23.6 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    33 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    239.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

    321.2 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

  • General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED

    321.4 ft. - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED

Observations (15)

DistanceCodeObservation
11.8FM
321.2MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0MWL
33CM
321.4MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
23.6FS
10.8CL
8.5CM
239.1FM
239.1CM
316.6FM
0AMH02 1146
321.4AMH02 1145

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-07-31T23:58:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false