- Date
- 10/01/2019
- W/O
- 0795645
- Weather
- Dry
- Operator/Surveyor
- IGNACIO
- Sewer ID
- Z00791
- PipeID
- P16903
- Time
- 10:19 AM
- Certificate
- U-115-06022628
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Jetting
- Media Label
- G8094
- Sewer Name
- 22 BEN LOMOND TRUNK
- City
- GLENDORA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 21
- Purpose
- Maintenance Related
- Project
- 20191001MI_BEN_LOMOND_TRUNK
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 22 0560
- Downstream MH
- 22 0561
- Dir. of Survey
- Upstream
- Length Surveyed
- 377.5 ft.
- Total Length
- 377.5 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 2
- O&M Quick
- 2200
- O&M Rating
- 4
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 7
Pipe schematic from manhole 22 0560 to 22 0561 Observation photos (5)

9.6 ft. - General Observation - MAG COAT, FROM 8 TO 4 OCLOCK, 80%

207.1 ft. - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

376.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

377.1 ft. - General Observation - CONNECTION AT MH, 12 OCLOCK, ACTIVE

377.5 ft. - Upstream Manhole, Survey Ends - 10:52 AM