Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 23, 2019, 10:10 AM
  • H 1356_H 0425A_23072019_032740.mp4

Date
07/23/2019
W/O
777336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00180
PipeID
P26723
Time
3:10 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6644
Sewer Name
H JOINT OUTFALL H - UNIT 5D
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_777336_TV15113_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
H 0425A
Downstream MH
H 1356
Dir. of Survey
Upstream
Length Surveyed
362.2 ft.
Total Length
362.2 ft.
Structural Index
2
Structural Quick
3M2M
Structural Rating
346
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
490
Pipe schematic from manhole H 0425A to H 1356
MH: H 0425AMH: H 1356upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 AND 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - H 13561.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish108.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"252.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"261 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"343.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start357.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start360.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start362.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK362.2 ft. AMH - Downstream Manhole, Survey Begins - H 0425A362.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE362.2 ft. MWM - Water Mark, 25 %of cross sectional area362.2 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
360.6SAV
150.1TF
0AMHH 0425A
0MGOCOCKROACHES IN MANHOLE
0MWM
362.2MGOACTIVE CONNECTION AT MH 9 AND 3 O'CLOCK
360.6DAGS
253.9TBA
2DAGS
360.6SSS
184.7TB
18.8SAV
110TF
0MWL
101.2TFA
362.2AMHH 1356
4.6SSS

Properties (6)

additional_info
SC378311
custom_field_two
3
customer
LACSD
datetime
2019-07-23T03:10:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false