Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 23, 2019, 06:31 AM
  • H 0430_H 0429_22072019_234916.mp4

Date
07/22/2019
W/O
777336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00180
PipeID
P10885
Time
11:31 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6644
Sewer Name
H JOINT OUTFALL H - UNIT 5D
City
SOUTH EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_777336_TV15113_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 0430
Downstream MH
H 0429
Dir. of Survey
Downstream
Length Surveyed
389 ft.
Total Length
389 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
385
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
539
Pipe schematic from manhole H 0430 to H 0429
MH: H 0430MH: H 0429downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 04300 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start136.2 ft. MGO - General Observation - MAGNEZIUM H.O COATING343.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"387 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish387 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish387 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish389 ft. MGO - General Observation - COCKROACHES IN MANHOLE389 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK389 ft. AMH - Downstream Manhole, Survey Ends - H 0429

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    389 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
389MGOCOCKROACHES IN MANHOLE
3.1SAP
3.1SSS
387SAP
136.2MGOMAGNEZIUM H.O COATING
0MWM
0MGOCOCKROACHES IN MANHOLE
389MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2DAGS
389AMHH 0429
0MWL
387SSS
0AMHH 0430
387DAGS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
343.3TBA
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC378311
custom_field_two
3
customer
LACSD
datetime
2019-07-22T23:31:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false