Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2019, 08:04 AM
  • H 0428_H 0427_24072019_012259.mp4

Date
07/24/2019
W/O
777336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00180
PipeID
P10883
Time
1:04 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6645
Sewer Name
H JOINT OUTFALL H - UNIT 5D
City
SOUTH EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_777336_TV15113_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 0428
Downstream MH
H 0427
Dir. of Survey
Downstream
Length Surveyed
412.2 ft.
Total Length
412.2 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
395
O&M Index
2
O&M Quick
3N2O
O&M Rating
395
Overall Index
2
Overall Quick
Overall Rating
790
Pipe schematic from manhole H 0428 to H 0427
MH: H 0428MH: H 0427downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 04280 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.3 ft. MGO - General Observation - MAG COATING THROUGHOUT15.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start15.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start24.3 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS27.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"283 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"410.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish410.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish410.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish410.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish412 ft. MGO - General Observation - REBAR VISIBLE THROUGHOUT THE REACH, 9 TO 3 OCLOCK412.2 ft. AMH - Downstream Manhole, Survey Ends - H 0427412.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK412.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE412.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    15.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    412.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
27.1TBA
15.5SAP
410.9SSS
410.9DAGS
412.2AMHH 0427
412.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
15.5SSS
0MWM
412MGOREBAR VISIBLE THROUGHOUT THE REACH, 9 TO 3 OCLOCK
0MWL
0AMHH 0428
410.9SAP
412.2MGOCOCKROACHES IN MANHOLE
283TBA
0MGOCOCKROACHES IN MANHOLE
412.2MGOCONNECTION AT MH 9 O'CLOCK
199.8TBA
3.3MGOMAG COATING THROUGHOUT
24.3DSZDEBRIS
2DAGS
410.9DSZ

Properties (6)

additional_info
SC378312
custom_field_two
2
customer
LACSD
datetime
2019-07-24T01:04:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false