Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2019, 08:23 AM
  • H 0427_H 0426_24072019_014259.mp4

Date
07/24/2019
W/O
777336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00180
PipeID
P10882
Time
1:23 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6645
Sewer Name
H JOINT OUTFALL H - UNIT 5D
City
SOUTH EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
32
Purpose
Routine Assessment
Project
WO_777336_TV15113_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 0427
Downstream MH
H 0426
Dir. of Survey
Downstream
Length Surveyed
404 ft.
Total Length
404 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
375
O&M Index
2
O&M Quick
2X00
O&M Rating
246
Overall Index
2
Overall Quick
Overall Rating
621
Pipe schematic from manhole H 0427 to H 0426
MH: H 0427MH: H 0426downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 04270 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.5 ft. MGO - General Observation - MAG COATING THROUGHOUT29.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start29.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start187.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS201.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"293.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"402.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish402.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish402.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE402.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish402.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish404 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK404 ft. AMH - Downstream Manhole, Survey Ends - H 0426404 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    29.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    402.2 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - COCKROACHES IN MANHOLE

    404 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
402.2DSZ
402.2SSS
3.5MGOMAG COATING THROUGHOUT
0MGOCOCKROACHES IN MANHOLE
0AMHH 0427
2DAGS
293.3TBA
0MWL
0MWM
404MGOACTIVE CONNECTION AT MH 9 O'CLOCK
29.6SSS
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
402.2MGOCOCKROACHES IN MANHOLE
201.2TBA
187.7DSZDEBRIS
29.6SAP
404AMHH 0426
402.2DAGS
404MGOCOCKROACHES IN MANHOLE
402.2SAP

Properties (6)

additional_info
SC378312
custom_field_two
3
customer
LACSD
datetime
2019-07-24T01:23:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false