Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 23, 2019, 08:33 AM
  • H 0424_H 0423_23072019_015624.mp4

Date
07/23/2019
W/O
777336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00180
PipeID
P10879
Time
1:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6644
Sewer Name
H JOINT OUTFALL H - UNIT 5D
City
SOUTH EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
32
Purpose
Routine Assessment
Project
WO_777336_TV15113_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 0424
Downstream MH
H 0423
Dir. of Survey
Downstream
Length Surveyed
700.4 ft.
Total Length
700.4 ft.
Structural Index
3
Structural Quick
3Z2Z
Structural Rating
680
O&M Index
2
O&M Quick
2[00
O&M Rating
278
Overall Index
2
Overall Quick
Overall Rating
958
Pipe schematic from manhole H 0424 to H 0423
MH: H 0424MH: H 0423downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 04240 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start17.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start17.2 ft. MGO - General Observation - MAG COATING THROUGHOUT17.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start697.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish697.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish697.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish700.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE700.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK700.4 ft. AMH - Downstream Manhole, Survey Ends - H 0423

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    17.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    700.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
0MWM
0AMHH 0424
697.8SSS
697.8SAP
17.2SSS
17.2MGOMAG COATING THROUGHOUT
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2DAGS
700.4MGOCOCKROACHES IN MANHOLE
17.2SAP
0MWL
700.4MGOACTIVE CONNECTION AT MH 3 O'CLOCK
700.4AMHH 0423
697.8DAGS

Properties (6)

additional_info
SC378311
custom_field_two
3
customer
LACSD
datetime
2019-07-23T01:33:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false