Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2019, 10:54 AM
  • 01 0266_01 0265_24062019_041600.mp4

Date
06/24/2019
W/O
771921
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00218
PipeID
P01312
Time
3:54 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5588
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_771921_TV01204_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0266
Downstream MH
01 0265
Dir. of Survey
Downstream
Length Surveyed
335.8 ft.
Total Length
335.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L11
O&M Rating
133
Overall Index
2
Overall Quick
Overall Rating
133
Pipe schematic from manhole 01 0266 to 01 0265
MH: 01 0266MH: 01 0265downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02660 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK ACTIVE2 ft. MMC - Material Change, Other (state in comments) - CIPP2.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start112.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"139.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"208.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"269 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"333.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish335.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0265335.8 ft. MGO - General Observation - CONNECTION IN MH 9 OCLOCK CAPPED335.8 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK ACTIVE

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.9 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
335.8AMH01 0265
139.6TF
335.8MGOCONNECTION IN MH 9 OCLOCK CAPPED
0AMH01 0266
0VC
112.8TF
269TF
0MWL
0MWM
2.9DAGS
208.7TF
0MGOCONNECTION IN MH 3 OCLOCK ACTIVE
333.6DAGS
335.8MGOCONNECTION IN MH 3 OCLOCK ACTIVE
2MMCCIPP

Properties (7)

additional_info
SC377545
custom_field_two
3
customer
LACSD
datetime
2019-06-24T03:54:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIP LINER