Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 08:10 AM
  • 01 0235_01 0234A_21062019_012632.mp4

Date
06/21/2019
W/O
771921
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00218
PipeID
P01280
Time
1:10 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5589
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
WATTS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_771921_TV01204_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
01 0235
Downstream MH
01 0234A
Dir. of Survey
Downstream
Length Surveyed
142.5 ft.
Total Length
142.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 01 0235 to 01 0234A
MH: 01 0235MH: 01 0234Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02350 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start139 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish142.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0234A142.5 ft. VC - Vermin Cockroach142.5 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMH01 0235
0MWL
0MWM
2DAGS
142.5AMH01 0234A
142.5VC
139DAGS
142.5MGOCONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH

Properties (7)

additional_info
SC377544
custom_field_two
3
customer
LACSD
datetime
2019-06-21T01:10:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIP LINER