Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 08:59 AM
  • 01 0233_01 0232_21062019_021612.mp4

Date
06/21/2019
W/O
771921
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00218
PipeID
P01276
Time
1:59 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5589
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
WATTS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_771921_TV01204_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
01 0233
Downstream MH
01 0232
Dir. of Survey
Downstream
Length Surveyed
300.5 ft.
Total Length
300.5 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
2K11
O&M Rating
119
Overall Index
3
Overall Quick
Overall Rating
329
Pipe schematic from manhole 01 0233 to 01 0232
MH: 01 0233MH: 01 0232downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02331.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start29 ft. LFW - Lining Failure Wrinkled, at 12 o'clock, within 8 inches of joint: YES, Start29 ft. LFDL - Lining Failure Delaminating, at 03 o'clock, within 8 inches of joint: YES, Start180 ft. LFDL - Lining Failure Delaminating, at 03 o'clock, within 8 inches of joint: YES, Finish180 ft. LFW - Lining Failure Wrinkled, at 12 o'clock, within 8 inches of joint: YES, Finish250 ft. LFW - Lining Failure Wrinkled, at 02 o'clock, within 8 inches of joint: YES, Start297 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish299 ft. LFW - Lining Failure Wrinkled, at 02 o'clock, within 8 inches of joint: YES, Finish300.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0232

Observations (13)

DistanceCodeObservation
0MWM
0VC
297DAGS
299LFW
250LFW
180LFDL
1.5DAGS
0MWL
180LFW
29LFW
300.5AMH01 0232
29LFDL
0AMH01 0233

Properties (7)

additional_info
SC377544
custom_field_two
3
customer
LACSD
datetime
2019-06-21T01:59:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIP LINER