Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2019, 07:01 AM
  • J 0010_J 0009 _26072019_003718.mp4

Date
07/26/2019
W/O
777426
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00060
PipeID
P21401
Time
12:01 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6721
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
RFIR_WO_777426_TV08100_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0010
Downstream MH
J 0009
Dir. of Survey
Downstream
Length Surveyed
338.3 ft.
Total Length
338.3 ft.
Structural Index
3
Structural Quick
5L3L
Structural Rating
668
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
670
Pipe schematic from manhole J 0010 to J 0009
MH: J 0010MH: J 0009downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00100 ft. MWM - Water Mark, 40 %of cross sectional area0.1 ft. MGO - General Observation - ACTIVE CONN 3 O'CLOCK/ACTIVE2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start174.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - OPEN278 ft. LR - Alignment Right, 20 %335 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% MAG335 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish335 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"338 ft. MGO - General Observation - POSSIBLE CONN 3 O'CLOCK @ MH/UNKNOWN338.3 ft. AMH - Downstream Manhole, Survey Ends - J 0009

Observation photos (1)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
335SZ70% MAG
0.1MGOACTIVE CONN 3 O'CLOCK/ACTIVE
0MWL
335SRV
336.8SSS
0AMHJ 0010
338.3AMHJ 0009
2SZ70% MAG
2SAP
338MGOPOSSIBLE CONN 3 O'CLOCK @ MH/UNKNOWN
6SSS
0MWM
2SRV
174.7TFOPEN
336.8TBA
278LR
335SAP

Properties (6)

additional_info
SC378220
custom_field_two
3
customer
LACSD
datetime
2019-07-26T00:01:04-07:00
documentation
PROPIPE
is_lateral_inspection
false