Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2019, 06:21 AM
  • J 0012_J 0010 _26072019_000024.mp4

Date
07/25/2019
W/O
777426
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00060
PipeID
P11596
Time
11:21 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6721
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
RFIR_WO_777426_TV08100_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0012
Downstream MH
J 0010
Dir. of Survey
Downstream
Length Surveyed
216.2 ft.
Total Length
216.2 ft.
Structural Index
3
Structural Quick
3H2G
Structural Rating
209
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
209
Pipe schematic from manhole J 0012 to J 0010
MH: J 0012MH: J 0010downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 00120 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG12.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start70.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN109 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"116.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN154.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN176 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN214.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish215 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish215 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% MAG216.2 ft. AMH - Downstream Manhole, Survey Ends - J 0010216.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
12.5SSS
2SAP
0AMHJ 0012
70.1TBOPEN
109TBA
0MWM
215SAP
216.2AMHJ 0010
154.8TBOPEN
176TBOPEN
116.9TBOPEN
2SZ70% MAG
215SZ70% MAG
214.6SSS
211.3TBOPEN
216.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL

Properties (6)

additional_info
SC378220
custom_field_two
3
customer
LACSD
datetime
2019-07-25T23:21:13-07:00
documentation
PROPIPE
is_lateral_inspection
false