Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2019, 06:00 AM
  • J 0003A_J 0003 _31072019_235335.mp4

Date
07/31/2019
W/O
777426
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00060
PipeID
P11591
Time
11:00 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6728
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_777426_TV08100_JUL2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0003A
Downstream MH
J 0003
Dir. of Survey
Downstream
Length Surveyed
494.5 ft.
Total Length
494.6 ft.
Structural Index
3
Structural Quick
3R2R
Structural Rating
480
O&M Index
2
O&M Quick
2R00
O&M Rating
192
Overall Index
2
Overall Quick
Overall Rating
672
Pipe schematic from manhole J 0003A to J 0003
MH: J 0003AMH: J 0003downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 0003A0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG15 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start290 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"424.6 ft. RPP - Repair Patch, from 09 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE ABANDONED MH493 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% MAG493.2 ft. MGO - General Observation - NO MH AT 490 FT494.5 ft. AMH - Downstream Manhole, Survey Ends - J 0003494.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish494.5 ft. MGO - General Observation - RETURNING TO 490FT TO END SURVEY494.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish494.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    15 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Patch, from 09 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE ABANDONED MH

    424.6 ft. - Repair Patch, from 09 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE ABANDONED MH

Observations (16)

DistanceCodeObservation
493SZ70% MAG
15DAGS
0MWL
494.5AMHJ 0003
494.5DAGS
424.6RPPPOSSIBLE ABANDONED MH
0AMHJ 0003A
16.2SSS
0MWM
493.2MGONO MH AT 490 FT
494.5MGORETURNING TO 490FT TO END SURVEY
16.2SAV
494.5SAV
2SZ70% MAG
290TBA
494.5SSS

Properties (6)

additional_info
SC378227
custom_field_two
3
customer
LACSD
datetime
2019-07-31T23:00:20-07:00
documentation
PROPIPE
is_lateral_inspection
false