Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 2, 2019, 06:10 AM
  • 22 1060_22 1059 _01082019_233057.mp4

Date
08/01/2019
W/O
776941
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00812
PipeID
P17431
Time
11:10 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5949
Sewer Name
22 IRWINDALE TRUNK, SECTS 2,3,4,&5
City
IRWINDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_776941_TV22043_JUL2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 1060
Downstream MH
22 1059
Dir. of Survey
Downstream
Length Surveyed
302.4 ft.
Total Length
302.4 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
180
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
184
Pipe schematic from manhole 22 1060 to 22 1059
MH: 22 1060MH: 22 1059downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN0 ft. AMH - Upstream Manhole, Survey Begins - 22 10600 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 20% MAG61.5 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 8" - CAPPED113.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN166.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN218.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN266.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"300 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG300 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish302.4 ft. AMH - Downstream Manhole, Survey Ends - 22 1059

Observation photos (6)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 8" - CAPPED

    61.5 ft. - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 8" - CAPPED

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN

    113.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN

    166.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN

    218.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    266.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
2SAP
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
300SZ65% MAG
0AMH22 1060
300SAP
0MGOROACHES @ MH
166.3TBUNKNOWN
113.6TBUNKNOWN
61.5TFCAPPED
0MWM
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
302.4AMH22 1059
266.7TFC
218.2TBUNKNOWN
0MWL
2SZ20% MAG

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-01T23:10:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false