Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 30, 2019, 10:43 AM
  • 08 0141A_08 0141 _30072019_040215.mp4

Date
07/30/2019
W/O
776939
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00006
PipeID
P00198
Time
3:43 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6726
Sewer Name
08 FIGUEROA STREET TRUNK
City
GARDENA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_776939_TV08002_JUL2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
08 0141A
Downstream MH
08 0141
Dir. of Survey
Downstream
Length Surveyed
233.9 ft.
Total Length
233.9 ft.
Structural Index
3
Structural Quick
4H3H
Structural Rating
410
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
410
Pipe schematic from manhole 08 0141A to 08 0141
MH: 08 0141AMH: 08 0141downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O' CLOCK AT MH/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 08 0141A0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MMC - Material Change, Concrete pipe (non-reinfored)2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. MGO - General Observation - STEAM IN SEWER5.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"161.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"231 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish232.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish233.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish233.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0141

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
2MMC
161.9TFC
5.5MGOSTEAM IN SEWER
233.9AMH08 0141
0MWL
233.5SAP
0MGOSERVICE CONNECTION AT 9 O' CLOCK AT MH/ACTIVE
231SSS
0AMH08 0141A
232.1FM
5.5FM
61.4TFC
5.5SAP
0MWM
2SSS

Properties (6)

additional_info
SC378225
custom_field_two
3
customer
LACSD
datetime
2019-07-30T03:43:49-07:00
documentation
PROPIPE
is_lateral_inspection
false