Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2019, 10:45 AM
  • 01 0567_01 0566_02222019_034220.mp4

Date
02/22/2019
W/O
750737
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00194
PipeID
P01054
Time
2:45 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6281
Sewer Name
01 ALAMEDA STREET EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_750737_TV01001_FEB2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
01 0567
Downstream MH
01 0566
Dir. of Survey
Downstream
Length Surveyed
371.7 ft.
Total Length
371.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 01 0567 to 01 0566
MH: 01 0567MH: 01 0566downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 05670 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area5.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6 ft. MGO - General Observation - MAG COAT101.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"368.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish371.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0566371.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    6 ft. - General Observation - MAG COAT

Observations (9)

DistanceCodeObservation
0AMH01 0567
0MWL
6MGOMAG COAT
371.7AMH01 0566
368.6SAP
371.7MGOCONNECTION AT MH 9 O'CLOCK
0MWM
5.9SAP
101.1TF

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-02-22T02:45:43-08:00
documentation
PROPIPE
is_lateral_inspection
false