Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2019, 02:43 PM
  • H 0678_H 0677_08092019_074418.mp4

Date
08/09/2019
W/O
766531
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00941
PipeID
P11085
Time
7:43 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6741
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
WO_766531_TV18175_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Upstream MH
H 0677
Downstream MH
H 0678
Dir. of Survey
Upstream
Length Surveyed
214.1 ft.
Total Length
214.1 ft.
Structural Index
2
Structural Quick
312G
Structural Rating
87
O&M Index
2
O&M Quick
2G1A
O&M Rating
93
Overall Index
2
Overall Quick
Overall Rating
180
Pipe schematic from manhole H 0677 to H 0678
MH: H 0677MH: H 0678upstream0 ft. MSA - Survey Abandoned - DOWNWARD ALIGNMENT0.1 ft. LL - Alignment Left, 5 %, Finish0.1 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.1 ft. MGO - General Observation - APPEARS TO BE SIPHON DOWNLEG7.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 8"12.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 18"16.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES54.7 ft. LL - Alignment Left, 5 %, Start105.3 ft. MWL - Water Level, 50 %of cross sectional area136.4 ft. MGO - General Observation - MAG COATING ATTATCHED203.3 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start209.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start214.1 ft. MWM - Water Mark, 40 %of cross sectional area214.1 ft. AMH - Downstream Manhole, Survey Begins - H 0677214.1 ft. MWL - Water Level, 35 %of cross sectional area

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    197.7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
214LL
159.4LL
214DSC
214SSS
10.8DSC
197.7SAP
77.7MGOMAG COATING ATTATCHED
0MWM
206.9TB
0AMHH 0677
0MWL
108.8MWL
201.2TFC
4.5SSS
214.1MSADOWNWARD ALIGNMENT
214MGOAPPEARS TO BE SIPHON DOWNLEG