Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2019, 06:03 PM
  • H 0688_H 0687_07312019_110349.mp4

Date
07/31/2019
W/O
766531
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00941
PipeID
P11095
Time
11:03 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6772
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
WO_766531_TV18175_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0687
Downstream MH
H 0688
Dir. of Survey
Upstream
Length Surveyed
167.6 ft.
Total Length
167.7 ft.
Structural Index
3
Structural Quick
3E2E
Structural Rating
160
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
160
Pipe schematic from manhole H 0687 to H 0688
MH: H 0687MH: H 0688upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 06882.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish164.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start164.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start164.6 ft. MGO - General Observation - MAG COATING THROUGHOUT REACH167.7 ft. MWM - Water Mark, 45 %of cross sectional area167.7 ft. AMH - Downstream Manhole, Survey Begins - H 0687167.7 ft. MWL - Water Level, 45 %of cross sectional area

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT REACH

    3.1 ft. - General Observation - MAG COATING THROUGHOUT REACH

Observations (9)

DistanceCodeObservation
0MWM
167.7AMHH 0688
3.1SSS
0AMHH 0687
3.1SAP
3.1MGOMAG COATING THROUGHOUT REACH
164.9SSS
164.9SAP
0MWL

Properties (6)

additional_info
SC378278
custom_field_two
3
customer
LACSD
datetime
2019-07-31T11:03:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false