Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2019, 05:55 PM
  • H 0687_H 0686_07312019_105624.mp4

Date
07/31/2019
W/O
766531
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00941
PipeID
P11094
Time
10:55 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6772
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
WO_766531_TV18175_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0686
Downstream MH
H 0687
Dir. of Survey
Upstream
Length Surveyed
78 ft.
Total Length
78 ft.
Structural Index
3
Structural Quick
3B2B
Structural Rating
75
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
75
Pipe schematic from manhole H 0686 to H 0687
MH: H 0686MH: H 0687upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 06872.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish76 ft. MGO - General Observation - MAG COATING THROUGHOUT REACH76 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start76 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start78 ft. AMH - Downstream Manhole, Survey Begins - H 068678 ft. MWL - Water Level, 45 %of cross sectional area78 ft. MWM - Water Mark, 45 %of cross sectional area

Observation photos (3)

  • General Observation - MAG COATING THROUGHOUT REACH

    2 ft. - General Observation - MAG COATING THROUGHOUT REACH

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
75.9SAP
0AMHH 0686
78AMHH 0687
75.9SSS
0MWL
2MGOMAG COATING THROUGHOUT REACH
2SAP
2SSS
0MWM

Properties (6)

additional_info
SC378278
custom_field_two
3
customer
LACSD
datetime
2019-07-31T10:55:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false