Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2019, 04:11 PM
  • H 0686_H 0685_07312019_091151.mp4

Date
07/31/2019
W/O
766531
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00941
PipeID
P11093
Time
9:11 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6772
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
WO_766531_TV18175_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0686
Downstream MH
H 0685
Dir. of Survey
Downstream
Length Surveyed
787.1 ft.
Total Length
787.1 ft.
Structural Index
3
Structural Quick
3^2^
Structural Rating
785
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
789
Pipe schematic from manhole H 0686 to H 0685
MH: H 0686MH: H 0685downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 06860 ft. MWL - Water Level, 55 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start108 ft. MGO - General Observation - MAG COATING THROUGHOUT REACH785.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish785.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish787.1 ft. AMH - Downstream Manhole, Survey Ends - H 0685

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT REACH

    108 ft. - General Observation - MAG COATING THROUGHOUT REACH

Observations (9)

DistanceCodeObservation
787.1AMHH 0685
0AMHH 0686
2SSS
2SAP
785.4SSS
785.4SAP
0MWL
0MWM
108MGOMAG COATING THROUGHOUT REACH

Properties (6)

additional_info
SC378278
custom_field_two
3
customer
LACSD
datetime
2019-07-31T09:11:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false