Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2019, 04:57 PM
  • H 0676_H 0675_08012019_095832.mp4

Date
08/01/2019
W/O
766531
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00941
PipeID
P11083
Time
9:57 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6773
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
EL MONTE
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
WO_766531_TV18175_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0676
Downstream MH
H 0675
Dir. of Survey
Downstream
Length Surveyed
453.4 ft.
Total Length
453.4 ft.
Structural Index
3
Structural Quick
3Q2Q
Structural Rating
450
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
450
Pipe schematic from manhole H 0676 to H 0675
MH: H 0676MH: H 0675downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06761.9 ft. MGO - General Observation - MAGNEZIUM H.O COATING THROUGHOUT REACH1.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start1.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start453.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish453.4 ft. AMH - Downstream, Survey Ends - H 0675453.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish453.4 ft. MGO - General Observation - MH# H 0675 DOES NOT EXIST. ENDED INSPECTION AT FOOTAGE PROVIDED.

Observation photos (3)

  • General Observation - MAGNEZIUM H.O COATING THROUGHOUT REACH

    1.9 ft. - General Observation - MAGNEZIUM H.O COATING THROUGHOUT REACH

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
453.4SAP
453.4AMHH 0675
1.9MGOMAGNEZIUM H.O COATING THROUGHOUT REACH
453.4SSS
1.9SAP
453.4MGOMH# H 0675 DOES NOT EXIST. ENDED INSPECTION AT FOOTAGE PROVIDED.
0MWM
0MWL
0AMHH 0676
1.9SSS

Properties (6)

additional_info
SC378279
custom_field_two
3
customer
LACSD
datetime
2019-08-01T09:57:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false