Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 19, 2019, 09:29 AM
  • Section#1_B 1396_B 1395__9192019__I0243R.mp4

Date
09/19/2019
W/O
0792526
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01126
PipeID
P25108
Time
2:29 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
I0243R
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
04
Purpose
Maintenance Related
Project
20190919MDM_JOINT_OUTFALL_B_UNIT_6J
Material
Vitrified Clay Pipe
Shape
Circular
Height
20 in.
Upstream MH
B 1396
Downstream MH
B 1395
Dir. of Survey
Downstream
Length Surveyed
208.4 ft.
Total Length
208.4 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
3322
O&M Rating
15
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole B 1396 to B 1395
MH: B 1396MH: B 1395downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:35AM35.1 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE-25% ROOTS36.7 ft. RML - Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: YES36.7 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6" - ACTIVE-90% ROOTS37.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN40.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN45.7 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YESR - 1%77.8 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 2%87.6 ft. RML - Roots Medium Lateral, from 02 to 05 o'clock, 25 %, within 8 inches of joint: YES87.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE-95% ROOTS90.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN125.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - POSSIBLE (MISSION) PIPE SEVERE SPALLING139.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB142.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB175.1 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN192.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB208.4 ft. AMH - Downstream Manhole, Survey Ends - 3:00AM-DROP MH

Observation photos (4)

  • Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: YES

    36.7 ft. - Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Medium Lateral, from 02 to 05 o'clock, 25 %, within 8 inches of joint: YES

    87.6 ft. - Roots Medium Lateral, from 02 to 05 o'clock, 25 %, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - POSSIBLE (MISSION) PIPE SEVERE SPALLING

    125.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - POSSIBLE (MISSION) PIPE SEVERE SPALLING

  • Downstream Manhole, Survey Ends - 3:00AM-DROP MH

    208.4 ft. - Downstream Manhole, Survey Ends - 3:00AM-DROP MH

Observations (19)

DistanceCodeObservation
40.5TFOPEN
139.7TFSTUB
45.7RFJ1%
36.7RML
87.6RML
208.4AMH3:00AM-DROP MH
36.7TBDACTIVE-90% ROOTS
142.2TFCSTUB
0MWL
87.6TFDACTIVE-95% ROOTS
192.4TFCSTUB
77.8RFJ2%
90.9TFOPEN
0MWM
175.1TBOPEN
125.4SSSPOSSIBLE (MISSION) PIPE SEVERE SPALLING
37.4TFOPEN
0AMH2:35AM
35.1TFDACTIVE-25% ROOTS

Properties (5)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-09-19T02:29:44-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection