Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 08:36 AM
  • 01 0233A_01 0233_21062019_015012.mp4

Date
06/21/2019
W/O
771921
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00218
PipeID
P01277
Time
1:36 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5589
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
WATTS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_771921_TV01204_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
01 0233A
Downstream MH
01 0233
Dir. of Survey
Downstream
Length Surveyed
307.5 ft.
Total Length
307.5 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
57
O&M Index
2
O&M Quick
2R11
O&M Rating
195
Overall Index
2
Overall Quick
Overall Rating
252
Pipe schematic from manhole 01 0233A to 01 0233
MH: 01 0233AMH: 01 0233downstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH ACTIVE0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0233A0 ft. VC - Vermin Cockroach2 ft. LFW - Lining Failure Wrinkled, from 07 to 11 o'clock, within 8 inches of joint: YES, Start3.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start96 ft. LFW - Lining Failure Wrinkled, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish120 ft. OBZ - Obstacles Other, 0 %of cross sectional area, from 10 to 02 o'clock, Start - SEAM TAPE PEELING210 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - OPEN305 ft. OBZ - Obstacles Other, 0 %of cross sectional area, from 01 to 02 o'clock, Finish - SEAM TAPE PEELING305.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish307.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0233

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
120OBZSEAM TAPE PEELING
305.6DAGS
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH ACTIVE
0MWL
0MWM
96LFW
3.3DAGS
0AMH01 0233A
0VC
305OBZSEAM TAPE PEELING
2LFW
307.5AMH01 0233
210TFOPEN

Properties (7)

additional_info
SC377544
custom_field_two
4
customer
LACSD
datetime
2019-06-21T01:36:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIP LINER