Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2019, 05:04 PM
  • 02 1871_02 1870_9162019_103454.mp4

Date
09/16/2019
W/O
0790964
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00246
PipeID
P04229
Time
10:04 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8081
Sewer Name
02 DOUGLAS AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Capital Improvement Program Assesment
Project
20190916DF_DOUGLAS_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1871
Downstream MH
02 1870
Dir. of Survey
Downstream
Length Surveyed
130.9 ft.
Total Length
130.9 ft.
Structural Index
3
Structural Quick
4633
Structural Rating
37
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
37
Pipe schematic from manhole 02 1871 to 02 1870
MH: 02 1871MH: 02 1870downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:32 AM0.1 ft. MWL - Water Level, 15 %of cross sectional area0.1 ft. MWM - Water Mark, 20 %of cross sectional area1.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. FS - Fracture Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open17.3 ft. MGP - General Photograph40.1 ft. MGP - General Photograph43 ft. FS - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES48.1 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES60.3 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES63.1 ft. FM - Fracture Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES65.5 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES68.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES73.3 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES79.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open80.9 ft. MGP - General Photograph86.1 ft. MGP - General Photograph120.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open128.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish128.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish128.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish130.9 ft. MGO - General Observation - Grease Throughout The Reach (5%)130.9 ft. MGO - General Observation - Conn. @ Mh, 5 O' Clock. UNKNOWN130.9 ft. AMH - Downstream Manhole, Survey Ends - 11:04 AM

Observation photos (14)

  • Upstream Manhole, Survey Begins - 10:32 AM

    0 ft. - Upstream Manhole, Survey Begins - 10:32 AM

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES

    7 ft. - Fracture Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES

  • General Photograph

    17.3 ft. - General Photograph

  • General Photograph

    40.1 ft. - General Photograph

  • Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    43 ft. - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    48.1 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    60.3 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    63.1 ft. - Fracture Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    65.5 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    68.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    73.3 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • General Photograph

    80.9 ft. - General Photograph

  • General Photograph

    86.1 ft. - General Photograph

Observations (27)

DistanceCodeObservation
48.1CS
40.1MGP
60.3FM
130.9MGOGrease Throughout The Reach (5%)
0AMH10:32 AM
17.3MGP
7FS
7FM
128.4FM
80.9MGP
128.4CM
43FS
0.1MWL
128.4SSS
8.7TFOpen
73.3FM
86.1MGP
130.9MGOConn. @ Mh, 5 O' Clock. UNKNOWN
68.2FM
2SSS
0.1MWM
79.8TFOpen
130.9AMH11:04 AM
120.6TFOpen
63.1FM
65.5FM
1.7CM

Properties (5)

custom_field_three
MULTIPLE FRACTURES THROUGHOUT
customer
LACSD
datetime
2019-09-16T10:04:13-07:00
documentation
FRANKLIN, IGNACIO, RUVALCABA, BRAR
is_lateral_inspection
false