Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2019, 08:19 AM
  • 02 0032A_02 0032_16072019_013010.mp4

Date
07/16/2019
W/O
771913
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00234
PipeID
P03064
Time
1:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6634
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_771913_TV02341_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0032
Downstream MH
02 0032A
Dir. of Survey
Upstream
Length Surveyed
182.3 ft.
Total Length
182.3 ft.
Structural Index
3
Structural Quick
3D21
Structural Rating
71
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
143
Pipe schematic from manhole 02 0032 to 02 0032A
MH: 02 0032MH: 02 0032Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 0032A0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish29.1 ft. JSL - Joint Separated Large36.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start180.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start182.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE182.3 ft. MWL - Water Level, 10 %of cross sectional area182.3 ft. AMH - Downstream Manhole, Survey Begins - 02 0032182.3 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    63.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Joint Separated Large

    153.2 ft. - Joint Separated Large

  • General Observation - COCKROACHES IN MANHOLE

    182.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
2DAGS
182.3AMH02 0032A
63.5CM
0MGOCOCKROACHES IN MANHOLE
0MWL
0AMH02 0032
146.1TFC
180.2CM
182.3MGOCOCKROACHES IN MANHOLE
0MWM
182.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
153.2JSL
180.2DAGS

Properties (6)

additional_info
SC378301
custom_field_two
3
customer
LACSD
datetime
2019-07-16T01:19:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false