Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2019, 09:01 AM
  • 02 0030_02 0029_16072019_021350.mp4

Date
07/16/2019
W/O
771913
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00234
PipeID
P03061
Time
2:01 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6634
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_771913_TV02341_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0030
Downstream MH
02 0029
Dir. of Survey
Downstream
Length Surveyed
330.6 ft.
Total Length
330.6 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
210
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
342
Pipe schematic from manhole 02 0030 to 02 0029
MH: 02 0030MH: 02 0029downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 00300 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start27.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start30.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"145.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"247.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start313 ft. B - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES327.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish327.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES327.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish328.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"330.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0029330.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    27.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    292.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    327.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
145.4TFA
313B
247.7TFC
327.8CM
292.2FL
327.8FM
30.6TFC
327.8FL
330.6AMH02 0029
330.6DAGS
328.4TB
0AMH02 0030
148.3TFC
0MWM
2DAGS
198.6TBA
0MWL
27.8CM

Properties (6)

additional_info
SC378301
custom_field_two
2
customer
LACSD
datetime
2019-07-16T02:01:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false