Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2019, 06:26 AM
  • 02 0012_02 0011_15072019_233936.mp4

Date
07/15/2019
W/O
771913
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00234
PipeID
P03038
Time
11:26 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6634
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_771913_TV02341_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0012
Downstream MH
02 0011
Dir. of Survey
Downstream
Length Surveyed
391.6 ft.
Total Length
391.6 ft.
Structural Index
3
Structural Quick
4B3F
Structural Rating
166
O&M Index
2
O&M Quick
412O
O&M Rating
160
Overall Index
3
Overall Quick
Overall Rating
326
Pipe schematic from manhole 02 0012 to 02 0011
MH: 02 0012MH: 02 0011downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 02 00122 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start48.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"55.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish88.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES88.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"197.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES202 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start209.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"246.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"333.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"363.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"370.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish370.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start390.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish390.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish391.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0011

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    88.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    197.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    202 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    370.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0MWL
246.2TFC
363.8TFA
390.9FM
390.9DAGS
0MWM
88.8CL
48.8TFC
88.8TF
2.4FM
370.6CM
333.7TB
0MGOCOCKROACHES IN MANHOLE
197.2CL
0AMH02 0012
391.6AMH02 0011
55.8FM
202CM
370.6FM
2DAGS
209.7TF

Properties (6)

additional_info
SC378301
custom_field_two
2
customer
LACSD
datetime
2019-07-15T23:26:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false