Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2019, 05:01 AM
  • 02 0009_02 0008_15072019_215237.mp4

Date
07/15/2019
W/O
771913
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00234
PipeID
P03035
Time
10:01 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6634
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_771913_TV02341_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0009
Downstream MH
02 0008
Dir. of Survey
Downstream
Length Surveyed
371.1 ft.
Total Length
371.1 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
2
O&M Quick
2N11
O&M Rating
147
Overall Index
2
Overall Quick
Overall Rating
306
Pipe schematic from manhole 02 0009 to 02 0008
MH: 02 0009MH: 02 0008downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 00090 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start102.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start117.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"186.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"262.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"317.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"317.4 ft. RFL - Roots Fine Lateral, at 12 o'clock368.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish368.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish371.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE371.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0008

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    102.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, at 12 o'clock

    317.4 ft. - Roots Fine Lateral, at 12 o'clock

Observations (16)

DistanceCodeObservation
117.7TF
317.4RFL
368.3FL
371.1MGOCOCKROACHES IN MANHOLE
102.6FL
317.1TFA
262.1TFA
186.2TFA
0MWL
371.1AMH02 0008
0MWM
2DAGS
0AMH02 0009
0MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
368.3DAGS

Properties (6)

additional_info
SC378301
custom_field_two
2
customer
LACSD
datetime
2019-07-15T22:01:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false