Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2019, 08:32 AM
  • Section#3_B 0477_B 0476__9162019__I0230R.mp4

Date
09/16/2019
W/O
O788117
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00094
PipeID
P09002
Time
1:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0236R
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
06
Purpose
Maintenance Related
Project
20190916MDM_JOINT_OUTFALL_B_UNIT_5D
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
B 0476
Downstream MH
B 0477
Dir. of Survey
Upstream
Length Surveyed
265.8 ft.
Total Length
265.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3422
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
20
Pipe schematic from manhole B 0476 to B 0477
MH: B 0476MH: B 0477upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:20AM15.6 ft. RFJ - Roots Fine Joint, from 08 to 12 o'clock, within 8 inches of joint: YESR - 2%26.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB28.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB35.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN43.6 ft. RML - Roots Medium Lateral, from 02 to 04 o'clock, 5 %, within 8 inches of joint: YES43.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN 80% ROOTS86.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB87.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB97.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE97.6 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR140.3 ft. RFL - Roots Fine Lateral, from 02 to 04 o'clock - 3%140.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN146 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR146 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB152.9 ft. RFL - Roots Fine Lateral, from 08 to 11 o'clock - 4%152.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN156.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - OPEN177.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN188.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN193.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN217.8 ft. RFJ - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR - 1%239.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN248.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-80% ROOTS248.8 ft. RML - Roots Medium Lateral, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YES265.8 ft. MGO - General Observation - MH CONN 6:00 OPEN265.8 ft. MWL - Water Level, 10 %of cross sectional area265.8 ft. MWM - Water Mark, 40 %of cross sectional area265.8 ft. AMH - Downstream Manhole, Survey Begins - 1:45AM

Observation photos (2)

  • Roots Medium Lateral, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YES

    17 ft. - Roots Medium Lateral, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR

    119.8 ft. - Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR

Observations (29)

DistanceCodeObservation
239.6TFCSTUB
88.1TFOPEN
168.2TFACTIVE
222.2RML
17TFDOPEN-80% ROOTS
237.1TFCSTUB
222.2TFDOPEN 80% ROOTS
48RFJ1%
119.8RMJ
168.2RMJ
125.5RFL3%
17RML
112.9RFL4%
112.9TFOPEN
250.2RFJ2%
125.5TFOPEN
0MGOMH CONN 6:00 OPEN
0MWL
230.7TFOPEN
109.5TFOPEN
0MWM
72.2TFOPEN
119.8TFCSTUB
179.7TFCSTUB
265.8AMH2:20AM
0AMH1:45AM
178TFCSTUB
77.1TFOPEN
26.7TFOPEN

Properties (5)

additional_info
PRE CLEANING ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-09-16T01:32:28-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false