Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2019, 07:03 AM
  • Section#3_02 1140_02 1139__9132019__I0235.mp4

Date
09/13/2019
W/O
0787613
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00351
PipeID
P02923
Time
12:03 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0235
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Maintenance Related
Project
20190913VMR_GARFIELD_AVE_EXTENSION_TRUNK
Sewer Type
CB
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1140
Downstream MH
02 1139
Dir. of Survey
Downstream
Length Surveyed
296.8 ft.
Total Length
296.8 ft.
Structural Index
2
Structural Quick
3322
Structural Rating
14
O&M Index
1
O&M Quick
2214
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole 02 1140 to 02 1139
MH: 02 1140MH: 02 1139downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:15 AM0 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"0 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"11.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES11.8 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES15.9 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES19.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES24.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES28.2 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES32.1 ft. RFC - Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES36.7 ft. RFJ - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR68.8 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR80.5 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR138.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - OPEN143 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"177.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"228.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"263.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"290.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"295.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES - Thrughout the reach295.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES - Thrughout the reach296.8 ft. AMH - Downstream Manhole, Survey Ends - 01:05 am

Observations (22)

DistanceCodeObservation
19.8CM
36.7RFJ
28.2CM
0AMH12:15 AM
0TFA
11.8CL
138.8TFOPEN
32.1RFC
228.5TFC
295.3DAGSThrughout the reach
15.9CM
295.3DAGSThrughout the reach
24.1CL
296.8AMH01:05 am
290.5TFC
263.1TFC
11.8CC
68.8RFJ
143TFC
0TFC
80.5RFJ
177.2TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-09-13T00:03:00-07:00
documentation
REVELES, BRAR
is_lateral_inspection
false