Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2019, 07:02 AM
  • Section#2_02 1141_02 1140__9132019__I0235.mp4

Date
09/13/2019
W/O
0787613
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00351
PipeID
P02924
Time
12:02 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0235
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Maintenance Related
Project
20190913VMR_GARFIELD_AVE_EXTENSION_TRUNK
Sewer Type
CB
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1141
Downstream MH
02 1140
Dir. of Survey
Downstream
Length Surveyed
317.7 ft.
Total Length
317.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
332X
O&M Rating
264
Overall Index
2
Overall Quick
Overall Rating
264
Pipe schematic from manhole 02 1141 to 02 1140
MH: 02 1141MH: 02 1140downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03:40 am1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Start1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES, Start27 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"75.6 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 2"78.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"129.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"169.2 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR179.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"180.9 ft. RMJ - Roots Medium Joint, from 02 to 03 o'clock, 5 %, within 8 inches of joint: YESR230.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"231.2 ft. RMJ - Roots Medium Joint, from 02 to 03 o'clock, 5 %, within 8 inches of joint: YESR247.6 ft. RMJ - Roots Medium Joint, from 02 to 03 o'clock, 5 %, within 8 inches of joint: YESR250.8 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 4"275.6 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR295.9 ft. RFJ - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR315 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Finish315 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES, Finish317.7 ft. AMH - Downstream Manhole, Survey Ends - 04:15 am317.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 8"317.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 8"

Observation photos (1)

  • Roots Medium Joint, from 02 to 03 o'clock, 5 %, within 8 inches of joint: YESR

    180.9 ft. - Roots Medium Joint, from 02 to 03 o'clock, 5 %, within 8 inches of joint: YESR

Observations (23)

DistanceCodeObservation
247.6RMJ
0MWM
169.2RFJ
0MWL
180.9RMJ
27TFC
179.3TFC
315DAGS
78.2TFC
230.2TFC
0AMH03:40 am
275.6RFJ
1.9DAGS
1.9DAGS
315DAGS
295.9RFJ
317.7AMH04:15 am
317.7TFA
129.1TFC
75.6TB
250.8TB
231.2RMJ
317.7TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-09-13T00:02:00-07:00
documentation
REVELES, BRAR
is_lateral_inspection
false