Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2019, 07:01 AM
  • Section#1_02 2108_02 1141__9132019__I0235.mp4

Date
09/13/2019
W/O
0787613
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00351
PipeID
P02925
Time
12:01 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0235
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Maintenance Related
Project
20190913VMR_GARFIELD_AVE_EXTENSION_TRUNK
Sewer Type
CB
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1141
Downstream MH
02 2108
Dir. of Survey
Upstream
Length Surveyed
303.8 ft.
Total Length
303.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2W11
O&M Rating
241
Overall Index
2
Overall Quick
Overall Rating
241
Pipe schematic from manhole 02 1141 to 02 2108
MH: 02 1141MH: 02 2108upstream0 ft. AMH - Downstream Manhole, Survey Ends - 03:35 am1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES, Finish1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Finish25.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"78.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"124.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"179.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"227.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"265.8 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR279.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"301.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Start301.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES, Start303.8 ft. MWL - Water Level, 25 %of cross sectional area303.8 ft. TFA - Tap Factory Made Active, at 04 o'clock, -, within 8 inches of joint: NO, 12"303.8 ft. MWM - Water Mark, 35 %of cross sectional area303.8 ft. AMH - Upstream Manhole, Survey Begins - 03:11 am

Observations (16)

DistanceCodeObservation
76.7TFC
0MWL
38RFJ
277.9TFC
0TFA
1.9DAGS
0MWM
124.2TFC
179TFC
24.5TFC
302.1DAGS
1.9DAGS
0AMH03:11 am
302.1DAGS
225.5TFC
303.8AMH03:35 am

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-09-13T00:01:00-07:00
documentation
REVELES, BRAR
is_lateral_inspection
false