Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2019, 10:56 AM
  • Section#19_01 0208_01 0207__9112019__I0233.mp4

Date
09/11/2019
W/O
0787675
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00202
PipeID
P01250
Time
3:56 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0233
Sewer Name
01 COMPTON AVENUE TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Capital Improvement Program Assesment
Project
20190905MDM_COMPTON_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
01 0208
Downstream MH
01 0207
Dir. of Survey
Downstream
Length Surveyed
199.9 ft.
Total Length
199.9 ft.
Structural Index
3
Structural Quick
3G2G
Structural Rating
201
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
201
Pipe schematic from manhole 01 0208 to 01 0207
MH: 01 0208MH: 01 0207downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:00AM2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE3.2 ft. MGO - General Observation - 75% MAG COAT START13.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN18.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN21.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN41.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG51.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN67.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN82.1 ft. MGO - General Observation - MAG COAT 50% START82.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG113.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN118.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN141.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN146.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN199.4 ft. MGO - General Observation - MAG COAT 50% FINISH199.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG199.4 ft. MGO - General Observation - MH CONN 9:00 ACTIVE199.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - FLAKING CONCRETE199.9 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (6)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

  • General Observation - 75% MAG COAT START

    3.2 ft. - General Observation - 75% MAG COAT START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    41.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - MAG COAT 50% START

    82.1 ft. - General Observation - MAG COAT 50% START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    82.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (23)

DistanceCodeObservation
0MWL
199.4MGOMAG COAT 50% FINISH
118.5TFOPEN
113.1TFOPEN
0MWM
41.9SAVSEVERE AGG
2SAVSEVERE AGG
18.2TFOPEN
199.4SAVSEVERE AGG
21.6TFOPEN
199.9AMH4:25AM
67.3TFOPEN
3.2MGO75% MAG COAT START
2SSSFLAKING CONCRETE
199.4MGOMH CONN 9:00 ACTIVE
51.7TFOPEN
82.5SAVSEVERE AGG
0AMH4:00AM
13.4TFOPEN
82.1MGOMAG COAT 50% START
146.6TFOPEN
199.4SSSFLAKING CONCRETE
141.8TFOPEN

Properties (6)

custom_field_three
SEVERE AGG PROJECTING
custom_field_two
3
customer
LACSD
datetime
2019-09-11T03:56:56-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection