Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2019, 08:17 AM
  • Section#11_01 0224_01 0223__992019__I0229.mp4

Date
09/09/2019
W/O
0787675
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00202
PipeID
P01266
Time
1:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0229
Sewer Name
01 COMPTON AVENUE TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
20190905MDM_COMPTON_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
01 0223
Downstream MH
01 0224
Dir. of Survey
Upstream
Length Surveyed
305.7 ft.
Total Length
305.7 ft.
Structural Index
3
Structural Quick
4J3K
Structural Rating
521
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
521
Pipe schematic from manhole 01 0223 to 01 0224
MH: 01 0223MH: 01 0224upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:05AM0.2 ft. MGO - General Observation - MH CONN 9;00 ACTIVE0.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - FLAKING CONCRETE0.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG6.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN76.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN81.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN122.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE163.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG167.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN170.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN183.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN218.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN246.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN267.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG274.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN294.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN297.8 ft. MGO - General Observation - 10" NRCP303.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE303.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG305.7 ft. AMH - Downstream Manhole, Survey Begins - 1:35AM305.7 ft. MGO - General Observation - MH CONN 9:00 OPEN305.7 ft. MGO - General Observation - MH CONN 3:00 ACTIVE305.7 ft. MWL - Water Level, 10 %of cross sectional area305.7 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (5)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 10" NRCP

    7.9 ft. - General Observation - 10" NRCP

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    38.2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    142.2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (26)

DistanceCodeObservation
38.2SAMSEVERE AGG
0AMH1:35AM
135TFOPEN
7.9MGO10" NRCP
183.5TFACTIVE
2SSSFLAKING CONCRETE
0MGOMH CONN 9:00 OPEN
305.5MGOMH CONN 9;00 ACTIVE
305.7AMH2:05AM
137.8TFOPEN
58.9TFOPEN
0MGOMH CONN 3:00 ACTIVE
11.1TFOPEN
2SAPSEVERE AGG
223.9TFOPEN
299.5TFOPEN
305.5SSSFLAKING CONCRETE
305.5SAPSEVERE AGG
0MWL
142.2SAMSEVERE AGG
0MWM
122.3TFOPEN
228.9TFOPEN
305.5SAMSEVERE AGG
31.2TFOPEN
87.2TFOPEN

Properties (6)

custom_field_three
MISSING SEVERE AGG
custom_field_two
3
customer
LACSD
datetime
2019-09-09T01:17:04-07:00
documentation
MARTIN,OLIVER 111 ,REVELES,BRAR
is_lateral_inspection
false