Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2019, 07:29 AM
  • Section#10_01 0223_01 0222__992019__I0229.mp4

Date
09/09/2019
W/O
0787675
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00202
PipeID
P01265
Time
12:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0229
Sewer Name
01 COMPTON AVENUE TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
20190905MDM_COMPTON_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
01 0223
Downstream MH
01 0222
Dir. of Survey
Downstream
Length Surveyed
316.9 ft.
Total Length
316.9 ft.
Structural Index
4
Structural Quick
4L23
Structural Rating
266
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
270
Pipe schematic from manhole 01 0223 to 01 0222
MH: 01 0223MH: 01 0222downstream0 ft. MGO - General Observation - MH CONN 3:00 OPEN0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - MH C0NN 9:00 ACTIVE0 ft. AMH - Downstream Manhole, Survey Begins - 12:35AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE7.9 ft. MGO - General Observation - 12" NRCP - POSSIBLE 10" NRCP18.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG31 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE71.5 ft. MWM - Water Mark, 50 %of cross sectional area76.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN79.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN183.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN193.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN216.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN236.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN252.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG284.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN289.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN316.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - FLAKING CONCRETE316.7 ft. MGO - General Observation - MH CONN 9:00 ACTIVE316.7 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG316.9 ft. AMH - Downstream Manhole, Survey Ends - 1:10AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 12" NRCP - POSSIBLE 10" NRCP

    7.9 ft. - General Observation - 12" NRCP - POSSIBLE 10" NRCP

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    18.4 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

    31 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - FLAKING CONCRETE

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    252.4 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (25)

DistanceCodeObservation
284.5TFOPEN
0MGOMH CONN 3:00 OPEN
0MWM
2SSSFLAKING CONCRETE
316.7SSSFLAKING CONCRETE
0MGOMH C0NN 9:00 ACTIVE
18.4SAMSEVERE AGG
2SAMSEVERE AGG
79.4TFOPEN
6TFACTIVE
183.4TFOPEN
316.7MGOMH CONN 9:00 ACTIVE
252.4SAMSEVERE AGG
193.2TFOPEN
316.9AMH1:10AM
289.8TFOPEN
236.5TFOPEN
316.7SAMSEVERE AGG
31SSSFLAKING CONCRETE
71.5MWM
0AMH12:35AM
0MWL
7.9MGO12" NRCP - POSSIBLE 10" NRCP
216.3TFOPEN
76.6TFOPEN

Properties (6)

custom_field_three
MISSING SEVERE AGG
custom_field_two
3
customer
LACSD
datetime
2019-09-09T00:29:04-07:00
documentation
MARTIN,OLIVER 111 ,BRAR
is_lateral_inspection
false