Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2019, 04:27 PM
  • 15 0851_15 0850_962019_093259.mp4

Date
09/06/2019
W/O
0788181
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00594
PipeID
P12629
Time
9:27 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
G8072
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20190905DF_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Material
NRCP
Shape
Circular
Height
8.399999618530273 in.
Upstream MH
15 0851
Downstream MH
15 0850
Dir. of Survey
Downstream
Length Surveyed
88.2 ft.
Total Length
88.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0851 to 15 0850
MH: 15 0851MH: 15 0850downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 9:28 AM0 ft. MWL - Water Level, 15 %of cross sectional area39.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"87 ft. MGP - General Photograph87 ft. MGP - General Photograph87 ft. LFBU - Lining Failure Bulges, from 10 to 02 o'clock, within 8 inches of joint: YES87 ft. LFZ - Lining Failure Other, from 01 to 04 o'clock, within 8 inches of joint: YES - HOLE IN LINER/ROOTS PUNCTURED88.2 ft. MSA - Survey Abandoned - 9:48 AM

Observation photos (4)

  • General Photograph

    87 ft. - General Photograph

  • General Photograph

    87 ft. - General Photograph

  • Lining Failure Bulges, from 10 to 02 o'clock, within 8 inches of joint: YES

    87 ft. - Lining Failure Bulges, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Lining Failure Other, from 01 to 04 o'clock, within 8 inches of joint: YES - HOLE IN LINER/ROOTS PUNCTURED

    87 ft. - Lining Failure Other, from 01 to 04 o'clock, within 8 inches of joint: YES - HOLE IN LINER/ROOTS PUNCTURED

Observations (11)

DistanceCodeObservation
0MGOConn. @ Mh, 3 O' Clock. Active
87MGP
0MWM
0MGOConn. @ Mh, 9 O' Clock. CAPPED
0AMH9:28 AM
0MWL
87MGP
39.4TFA
88.2MSA9:48 AM
87LFBU
87LFZHOLE IN LINER/ROOTS PUNCTURED

Properties (8)

additional_info
POST ROOT EVALUATION
custom_field_three
HOLE IN LINER/PUNCTURED BY ROOTS
custom_field_two
5
customer
LACSD
datetime
2019-09-06T09:27:42-07:00
documentation
FRANKLIN, CASTILLO, IGNACIO
is_lateral_inspection
false
lining
PVCP-Folded/Reformed