Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2019, 04:47 PM
  • 02 1342_02 1341_8262019_095303.mp4

Date
08/26/2019
W/O
0786986
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00238
PipeID
P03867
Time
9:47 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8064
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
20190826SHO_BELVEDERE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1342
Downstream MH
02 1341
Dir. of Survey
Downstream
Length Surveyed
326.5 ft.
Total Length
326.5 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 1342 to 02 1341
MH: 02 1342MH: 02 1341downstream0 ft. MGO - General Observation - ACTIVE CONNECTION IN THE MH @ 90 ft. AMH - Upstream Manhole, Survey Begins - MH 13420 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area4 ft. MGO - General Observation - SMALL AMOUNT OF MAG COAT THROUGHOUT36.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - VERY MINOR SPALLING52.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"60.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES91.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"170.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"243.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"326.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish326.5 ft. AMH - Downstream Manhole, Survey Ends - MH 1341

Observation photos (2)

  • General Observation - SMALL AMOUNT OF MAG COAT THROUGHOUT

    4 ft. - General Observation - SMALL AMOUNT OF MAG COAT THROUGHOUT

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - VERY MINOR SPALLING

    36.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - VERY MINOR SPALLING

Observations (13)

DistanceCodeObservation
170.8TF
0MGOACTIVE CONNECTION IN THE MH @ 9
52.6TF
60.3CM
243.2TF
4MGOSMALL AMOUNT OF MAG COAT THROUGHOUT
0AMHMH 1342
326.1SSS
91.7TFA
326.5AMHMH 1341
0MWL
0MWM
36.1SSSVERY MINOR SPALLING

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2019-08-26T09:47:21-07:00
documentation
OBREGON, YOUNG, CASTILLO
is_lateral_inspection