Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 12, 2019, 06:58 AM
  • 20 0424_20 0423 _12072019_001521.mp4

Date
07/11/2019
W/O
772198
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00749
PipeID
P19372
Time
11:58 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6632
Sewer Name
20 10TH STREET EAST CONNECTION TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_772198_TV20064_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
20 0424
Downstream MH
20 0423
Dir. of Survey
Downstream
Length Surveyed
355 ft.
Total Length
355 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
143
Pipe schematic from manhole 20 0424 to 20 0423
MH: 20 0424MH: 20 0423downstream0 ft. AMH - Upstream Manhole, Survey Begins - 20 04240 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start10.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"34 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.2 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES68.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"118 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"269.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"315.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"319 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"352.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish355 ft. AMH - Downstream Manhole, Survey Ends - 20 0423355 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    35.2 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
0AMH20 0424
34TFC
2DAGS
137.1TFA
315.8TFA
35.2CM
118TFC
226.9TFA
168.1TFC
355AMH20 0423
68.8TFC
0MWL
352.9DAGS
0MWM
269.4TFC
245.8TF
10.7TF
355MGOACTIVE CONNECTION AT MH 9 O'CLOCK
319TFC
75.2TFA
195.4TF

Properties (6)

additional_info
SC378199
custom_field_two
3
customer
LACSD
datetime
2019-07-11T23:58:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false