- Date
- 07/08/2019
- W/O
- 771793
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00677
- PipeID
- P14865
- Time
- 1:57 AM
- Certificate
- U-115-06022794
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K5928
- Sewer Name
- 18 LA HABRA HEIGHTS TRUNK, SECTION 1
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 22
- Purpose
- Routine Assessment
- Project
- RFIR_WO_771793_TV18011_JUN2019
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 8 in.
- Upstream MH
- 18 1011
- Downstream MH
- 18 1010
- Dir. of Survey
- Downstream
- Length Surveyed
- 92.3 ft.
- Total Length
- 92.3 ft.
- Structural Index
- 4
- Structural Quick
- 4431
- Structural Rating
- 21
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 21
Pipe schematic from manhole 18 1011 to 18 1010 Observation photos (6)

18 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

49.6 ft. - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES

68.7 ft. - Fracture Multiple, from 01 to 06 o'clock, within 8 inches of joint: YES

71.6 ft. - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

84.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

90.5 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES