Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2019, 09:28 AM
  • 18 1010_18 1009 _08072019_030448.mp4

Date
07/08/2019
W/O
771793
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00677
PipeID
P14864
Time
2:28 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5928
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_771793_TV18011_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 1010
Downstream MH
18 1009
Dir. of Survey
Downstream
Length Surveyed
341.6 ft.
Total Length
341.6 ft.
Structural Index
3
Structural Quick
4133
Structural Rating
13
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 18 1010 to 18 1009
MH: 18 1010MH: 18 1009downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 10100 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area7.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"21.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES24.5 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES25.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"42.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES76.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"157.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"202.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"222.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES226.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"308.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.1 ft. RML - Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: NO336.6 ft. RPP - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES - remark341.6 ft. AMH - Downstream Manhole, Survey Ends - 18 1009

Observation photos (15)

  • Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"

    7.8 ft. - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    21.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    24.5 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    25.7 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    42.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    76.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    100.5 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    157.6 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    202.9 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    222.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    226.7 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    305.6 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    308.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: NO

    308.1 ft. - Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: NO

  • Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES - remark

    336.6 ft. - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES - remark

Observations (19)

DistanceCodeObservation
7.8TF
0AMH18 1010
341.6AMH18 1009
202.9TF
336.6RPPremark
0MWM
226.7TF
222.5CM
0MWL
157.6TF
100.5TF
21.6CM
25.7TF
308.1TF
24.5FM
305.6TF
308.1RML
42.2CM
76.6TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-07-08T02:28:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false