Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2019, 10:08 AM
  • 18 1009_18 1008 _08072019_042342.mp4

Date
07/08/2019
W/O
771793
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00677
PipeID
P14863
Time
3:08 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5928
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_771793_TV18011_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 1009
Downstream MH
18 1008
Dir. of Survey
Downstream
Length Surveyed
288 ft.
Total Length
288 ft.
Structural Index
4
Structural Quick
4333
Structural Rating
21
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
26
Pipe schematic from manhole 18 1009 to 18 1008
MH: 18 1009MH: 18 1008downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 10092 ft. RFB - Roots Fine Barrell, at 12 o'clock2 ft. FS - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: NO17.9 ft. FS - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES17.9 ft. RMJ - Roots Medium Joint, from 07 to 08 o'clock, 15 %, within 8 inches of joint: YESR40.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.4 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES169.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"185.9 ft. FM - Fracture Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES187.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"240.3 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES246.4 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES247.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"288 ft. AMH - Downstream Manhole, Survey Ends - 18 1008

Observation photos (14)

  • Roots Fine Barrell, at 12 o'clock

    2 ft. - Roots Fine Barrell, at 12 o'clock

  • Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: NO

    2 ft. - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: NO

  • Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    17.9 ft. - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 07 to 08 o'clock, 15 %, within 8 inches of joint: YESR

    17.9 ft. - Roots Medium Joint, from 07 to 08 o'clock, 15 %, within 8 inches of joint: YESR

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    40.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    73.2 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    109.2 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    168.4 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    169.3 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES

    185.9 ft. - Fracture Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    187.2 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    240.3 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    246.4 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    247.3 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

Observations (18)

DistanceCodeObservation
17.9FS
288AMH18 1008
247.3TF
169.3TF
109.2TF
185.9FM
0MWL
73.2TF
0MWM
40.1TF
2RFB
2FS
168.4FM
187.2TF
17.9RMJ
240.3FM
0AMH18 1009
246.4FS

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-07-08T03:08:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false