- Date
- 07/17/2019
- W/O
- 771822
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z01126
- PipeID
- P25161
- Time
- 2:36 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K6635
- Sewer Name
- B JOINT OUTFALL B - UNIT 6J
- City
- PASADENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 16
- Purpose
- Routine Assessment
- Project
- RFIR_WO_771822_TV16066_JUN2019
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- B 1266
- Downstream MH
- B 1265
- Dir. of Survey
- Downstream
- Length Surveyed
- 71.1 ft.
- Total Length
- 71.1 ft.
- Structural Index
- 3
- Structural Quick
- 3B2B
- Structural Rating
- 70
- O&M Index
- 2
- O&M Quick
- 2B00
- O&M Rating
- 28
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 98
Pipe schematic from manhole B 1266 to B 1265 Observation photos (3)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start