Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 1, 2019, 11:56 AM
  • 02 1387_02 1386 _01072019_052229.mp4

Date
07/01/2019
W/O
772333
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00242
PipeID
P03905
Time
4:56 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5581
Sewer Name
02 CLOVERLAWN TRUNK
City
PARAMOUNT
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
31
Purpose
Routine Assessment
Project
WO_772333_TV02041_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1387
Downstream MH
02 1386
Dir. of Survey
Downstream
Length Surveyed
343.8 ft.
Total Length
343.8 ft.
Structural Index
2
Structural Quick
3524
Structural Rating
25
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
29
Pipe schematic from manhole 02 1387 to 02 1386
MH: 02 1387MH: 02 1386downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13870 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start20.2 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES30.2 ft. CS - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES32.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4"41.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"70.6 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES74.2 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES92.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"142.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"147.8 ft. CC - Crack Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES197 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"201.7 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES225.6 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES235.9 ft. FS - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES256.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES261.2 ft. SSS - Surface Spalling, at 12 o'clock, within 8 inches of joint: YES331.8 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES341.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish341.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish343.8 ft. AMH - Downstream Manhole, Survey Ends - 02 1386

Observation photos (13)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    20.2 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    30.2 ft. - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    70.6 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    74.2 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

    147.8 ft. - Crack Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    201.7 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    225.6 ft. - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    235.9 ft. - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    256.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, at 12 o'clock, within 8 inches of joint: YES

    261.2 ft. - Surface Spalling, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    331.8 ft. - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
0AMH02 1387
92.3TFC
0MWM
70.6CM
235.9FS
20.2CS
74.2CM
201.7CM
331.8FC
147.8CC
32.8TB
225.6CC
341.6DAGS
0MWL
41.7TFC
341.6DAE
256.6CM
142.7TFC
2.5DAE
197TFC
30.2CS
261.2SSS
343.8AMH02 1386
2.5DAGS

Properties (6)

additional_info
SC378253
custom_field_two
3
customer
LACSD
datetime
2019-07-01T04:56:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false