Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2017, 07:52 AM
  • 15 0729_15 0728 _08062017_024800.mp4

Date
06/08/2017
W/O
640598
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00616
PipeID
P12622
Time
12:52 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4544
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_640598_TV15132_JUN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0729
Downstream MH
15 0728
Dir. of Survey
Downstream
Length Surveyed
388.5 ft.
Total Length
388.5 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
231
O&M Index
2
O&M Quick
412N
O&M Rating
158
Overall Index
3
Overall Quick
Overall Rating
389
Pipe schematic from manhole 15 0729 to 15 0728
MH: 15 0729MH: 15 0728downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 07290 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area4.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.8 ft. MGO - General Observation - MAG COATING380.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish388.4 ft. LD - Alignment Down, 45 %388.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish388.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0728

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
388.5SAV
388.4LD
0AMH15 0729
380.1DAGS
0MWM
4.8SAV
4.8DAGS
4.8MGOMAG COATING
0MWL
388.5AMH15 0728

Properties (6)

additional_info
SC345359
custom_field_two
3
customer
LACSD
datetime
2017-06-08T00:52:11-07:00
documentation
PROPIPE
is_lateral_inspection
false