Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2019, 05:18 AM
  • 01 0279_01 0278_01072019_224103.mp4

Date
07/01/2019
W/O
771797
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00219
PipeID
P01327
Time
10:18 PM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5580
Sewer Name
01 STANFORD AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_771797_TV01062_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0279
Downstream MH
01 0278
Dir. of Survey
Downstream
Length Surveyed
333.1 ft.
Total Length
333.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2311
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 0279 to 01 0278
MH: 01 0279MH: 01 0278downstream0 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH ACTIVE0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02790 ft. MWL - Water Level, 35 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start4.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start64.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"66.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"115.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"118.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"136.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"157.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"182 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"184.6 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: YES, 4" - DEBRIS INSIDE188.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS236.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"239.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"284.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"286.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"328.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish330.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish330.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - DEBRIS333.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0278333.1 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
115.6TF
64.4TFC
239.4TF
182TF
330.2DAE
0VC
330.2DAGS
118.4TFC
333.1AMH01 0278
333.1MGOCONNECTIONS AT BOTH 3 AND 9 O' CLOCK AT MH ACTIVE
66.7TFC
4.7CM
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH ACTIVE
184.6TFBDEBRIS INSIDE
286.9TFC
2.4DAGS
2.4DAE
284.3TFC
0MWM
236.3TFC
0AMH01 0279
188.6DSZDEBRIS
136.1TF
328.6CM
157.4TF
330.2DSZDEBRIS
0MWL

Properties (6)

additional_info
SC378254
custom_field_two
3
customer
LACSD
datetime
2019-07-01T22:18:05-07:00
documentation
PRO PIPE
is_lateral_inspection
false